文章摘要
陈凌,龙震泽,邓斌,罗华东,廖强,丁玉栋.竖直三维内肋管管内变压器油自然对流换热特性[J].,2022,21(6):595-601
竖直三维内肋管管内变压器油自然对流换热特性
Natural-convection heat transfer characteristics of transformer oil in the vertical 3-D internally finned tube
投稿时间:2021-07-28  修订日期:2021-11-14
DOI:0.13738/j.issn.1671-8097.021215
中文关键词: 三维内肋管  田口法  自然对流  正交实验
英文关键词: 3-D internally finned tube  Taguchi method  natural convection  heat transfer
基金项目:
作者单位E-mail
陈凌 国网四川省电力公司电力科学研究院 cxxxz@163.com 
龙震泽 国网四川省电力公司电力科学研究院  
邓斌 重庆大学  
罗华东 重庆大学  
廖强 重庆大学  
丁玉栋* 重庆大学 dingyudong@cqu.edu.cn 
摘要点击次数: 167
全文下载次数: 102
中文摘要:
      利用田口法对具有不同肋结构参数的竖直三维内肋管管内变压器油自然对流换热特性进行了实验研究,获得了肋高、肋宽、轴向间距和周向间距等肋结构参数对管内自然对流换热性能的影响规律,提出了肋结构参数最佳组合。结果表明,变压器顶层油温从40℃变化至100℃,肋高和肋宽对换热性能的影响占比基本不变,周向间距的影响占比逐渐减小,轴向间距的影响占比逐渐增大;相比光管,三维内肋管的自然对流强化换热性能随顶层油温的增大而增加,变压器油自然对流Nu最大约为光管的1.75倍。拟合了竖直三维内肋管管内变压器油自然对流换热计算关联式,其与实验数据的最大偏差为±16%。
英文摘要:
      The natural-convection heat transfer characteristics of transformer oil inside the three-dimensional (3-D) internal-ly finned tubes were experimental investigated by using Taguchi method. The effects of fin structural parameters (fin height, axial fin pitch, fin width and circumferential fin pitch) on the performance of transformer oil nature-convection heat transfer in 3-D internally finned tubes were presented, the optimum combination of fin structural parameters was put forward. The results show that when the top oil temperature of transformer varied from 40 ℃ to 100 ℃, the influence of fin height and fin width on the heat transfer performance was barely changed, however the influence of circumferential fin pitch decreased gradually, and the influence of axial fin pitch increased gradu-ally. The nature-convection heat transfer augmentation of 3-D internally finned tube was increasingly apparent with the increasing of top oil temperature of transformer, the maximum Nusselt (Nu) number was approximately 1.75 times bigger than that of smooth tube in the scope of experiments. Finally, the empirical correlation of trans-former oil nature-convection heat transfer was proposed for vertical 3-D internally finned tube, the predicted val-ues of Nu number in agreement with the experimental values within the error of ±16 %.
查看全文   查看/发表评论  下载PDF阅读器